AWS D1.1 Inspection Report — Structural Beam Package, 12 CJP Welds

A structural fabrication shop completed beam-to-column connections for a mezzanine addition on an industrial building. The inspector evaluated 12 CJP groove welds on W14×53 members, statically loaded. Weld W7 was rejected for undercut at the root toe: depth measured at 3/64″ (0.047″), exceeding the statically loaded limit of 1/32″ (0.031″) for material ≤1″ thick. The contractor ground the toe, applied a repair pass, and re-inspection confirmed acceptance.
Document Preview
Weld Cost Breakdown — Generated by IronKit

Job Parameters

ProjectMezzanine addition — industrial building
InspectorJames R. Cole, CWI
Date2025-11-18
WPS ReferenceWPS-S-001 (FCAW-G, AWS D1.1)
Base MetalASTM A36 structural steel
FillerE71T-1C (0.045" FCAW wire)
Joint TypeCJP Groove
Service CategoryStatically Loaded
Total Welds Inspected12
Accepted11
Rejected1 (Weld W7 — undercut)

Cost Breakdown

Cost ComponentFormula / BasisUnit CostTotal
Crack Prohibition (Cl. 6.9.1)All 12 welds — no cracks observed$12.00$12.00
Fusion — Weld/Base Metal (Cl. 6.9.2)All 12 welds — complete fusion confirmed$12.00$12.00
Crater Cross Section (Cl. 6.9.3)All 12 welds — craters filled$12.00$12.00
Weld Profile, Fig. 5.4 (Cl. 6.9.4)All 12 welds — profile within limits$12.00$12.00
Weld Size Under-Run (Cl. 6.9.5)All 12 welds — no under-run over limit$12.00$12.00
Undercut (Cl. 6.9.6)W7 rejected: 3/64" depth (limit 1/32" for t<=1")$11.00$12.00
Porosity — Groove (Cl. 6.9.7)All 12 welds — no porosity observed$12.00$12.00
Total Direct Cost$0.00

Per-Unit Cost Summary

Total Welds12
Accepted11
Rejected1 (W7 — undercut at root toe)
Pass Rate91.7%
Overall DispositionREJECTED — pending corrective action on W7
Corrective ActionGrind toe, apply repair weld pass per WPS-S-001
Re-Inspection ResultACCEPTED — all 12 welds accepted after repair
Code ReferenceAWS D1.1:2020 Table 6.1, Cl. 6.9.6

Frequently Asked Questions

What is undercut and why did it cause a rejection?
Undercut is a groove melted into the base metal at the weld toe. AWS D1.1 Cl. 6.9.6 limits undercut depth to 1/32" for material 1" thick or less on statically loaded structures. Weld W7 measured 3/64" — about 50% over the limit. The correction is to grind the undercut area and apply a fill pass to restore the base metal profile, then re-inspect.
How is undercut depth measured?
Undercut is measured perpendicular to the base metal surface using calibrated bridge cam gauges or an undercut gauge. Depth is compared against the Table 6.1 limit for the applicable service category and material thickness.
When can a rejected weld be re-inspected?
After corrective action is completed per AWS D1.1 Cl. 5.25 (repair welding) or grinding to remove the rejectable condition. The CWI must re-inspect and accept the weld before final sign-off.